Bentel J408-2 (2-zone)
Bentel J408-2 (2-zone)
Kaina 15107 € su PVMPrekė išparduota.SusisiekiteDesigned and made according to EN54 and EN12094-1 standards (with J400-EXT extinguishment module), the J408 is a microprocessor based control panel for small to medium applications. 2 (J408-2) controlled, balanced, bypassable input zonesEach detection zone has an alarm-repeat output for selective management in the event of fire. The control panel has supervised, silenceable alarm-outputs for self-powered sirens, piezoelectric sirens, fire bells, flashers, telephone diallers, etc-
MAIN FEATURES:
- EN54 and EN12094-1 approved (with J400-EXT extinguishment module)
- 2 (J408-2) controlled, balanced, bypassable input zones
- Up to 32 devices can be connected to each zone: conventional fire detectors, alarm buttons, gas detectors
- Gas zone compatible with 4 – 20 mA gas detectors
- Manual call point recognition
- Programmable thresholds
- Missing detectors
- Day/Night mode
- Alarm verification time
- Programmable restoral and reset times
- One alarm-repeat output (open collector) for each input zone
- 2 supervised, silenceable, bypassable 24 V alarm output for the activation of piezoelectric sirens, fire bells and flashers
- Silenceable, bypassable alarm output, for the activation of 24 V self-powered sirens
- Silenceable fault-warning output for the activation of signalling and auxiliary devices
- Supervised fire output for telephone dialler activation
- Programmable open-collector output
- Alarm/fault memory up to next reset
- Command for silencing sirens
- Keypad commands require key or code
- Programmable from PC or keypad
- 50 events log viewed via PC
- RS485 bus for connecting up to 4 repeater panels
TECHNICAL FEATURES:- Power supply: 230 Vac ±10%
- 27.6 Vdc 1.5 A switching supply/battery-charger
- Compartment for two 12 V 7 Ah batteries
- Dimensions (wxhxd): 354x280x100 mm
- Weight (without batteries): max. 4 Kg
-